Installation, Operation
& Service Manual
Models UHA[S]
150, 175, 200, 225
250, 300, 350, 400
P/N 111101 N A 10 /0 7 Rev. D
UHA-Series
Tubular Unit Heaters
(Standard Range)
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Leave the building.
6. Immediately call your local gas
supplier after leaving the building.
Follow the gas suppliers
instructions.
7. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
WARNING
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the Installation, Operation and Service
Manual thoroughly before installing or servicing
this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Roberts-Gordon, LLC
1250 William Street
P. O . Box 4 4
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
www.rg-inc.com
© Copyright 2007 Roberts-Gordon, LLC
Quality in Any Language™
Combat
®
Seitenansicht 0
1 2 3 4 5 6 ... 47 48

Inhaltsverzeichnis

Seite 1 - (Standard Range)

Installation, Operation & Service ManualModels UHA[S]150, 175, 200, 225250, 300, 350, 400P/N 111101 N A 10 /0 7 Rev. DUHA-SeriesTubular Unit He

Seite 2

WARNINGFire HazardSome objects will catch fire or explode when placedclose to heater.Keep all flammable objects, liquids and vapors therequired cleara

Seite 3 - Roberts-Gordon, LLC

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES5SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES4.1 Gas CodesThe type of gas appearing on the nam

Seite 4

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL6 SECTION 5: MAJOR COMPONENTS 5.1 General Heaters are designed for installation above

Seite 5 - TABLE OF FIGURES

SECTION 6: VENTING7SECTION 6: VENTING6.1 VentingThis heater must be vented in accordance with the rules contained in this manual and with the followin

Seite 6

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL8 6.2.2 Separated Combustion Heaters (Models UHAS 150 - 400)The heaters are

Seite 7 - SECTION 1: HEATER SAFETY

SECTION 6: VENTING96.7 Vent MaterialVent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely

Seite 8

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL10 Figure 5: Standard Vented Heater - Common Vertical Vent TerminationRoof18"

Seite 9 - RITICAL CONSIDERATIONS

SECTION 6: VENTING11Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent TerminationVentTerminationListed Thimble throughCombustible W

Seite 10 - Installation Clearances

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL12 Figure 8: Concentric Vertical and Horizontal Vent TerminationVentAir Intake*Concen

Seite 11

SECTION 7: AIR SUPPLY13SECTION 7: AIR SUPPLY7.1 Separated Combustion InstallationWhen installed as a separated combustion heater, the air for combusti

Seite 13 - SECTION 6: VENTING

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL14 SECTION 8: GAS PIPINGWARNINGFire HazardConnect gas supply according to Figure 9.Ga

Seite 14

SECTION 9: WIRING15SECTION 9: WIRINGWARNINGElectrical Shock HazardDisconnect electrical power and gas supply beforeservicing.This appliance must be co

Seite 15

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL16 9.3 UHA(S) Series Internal Wiring DiagramBLUEBLACKBLACKORANGEORANGEYELLOWBROWNBLAC

Seite 16

SECTION 9: WIRING179.4 UHA(S) Series Ladder Wiring DiagramFLAMESENSORPRESSURE SWITCHTHERMOSTAT CONNECTION634521120 VACTRANSFORMERCOMBUSTION BLOWERCIRC

Seite 17 - Figure 7: Concentric Vent Box

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL18 9.5 Electrical Connection to the HeaterBX ConnectorJunction BoxFlexible ConduitBur

Seite 18 - 8" Dia. Single Wall

SECTION 10: OPERATION AND MAINTENANCE19SECTION 10: OPERATION AND MAINTENANCEInstallation, service, and annual inspection of the heater must be done by

Seite 19 - SECTION 7: AIR SUPPLY

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL20 Figure 10: Automatic Burner Control SequenceBurner Sequence for Ignition ControlFl

Seite 20 - Fire Hazard

SECTION 10: OPERATION AND MAINTENANCE2110.2.2 Start-Up the Gas Valve (All Gases)10.2.2.1 Check Burner Gas Pressure1. Remove the plug in the outlet (bu

Seite 21 - SECTION 9: WIRING

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL22 SECTION 11: USER INSTRUCTIONS11.1 User InstructionsThe UHA(S) Series heaters are f

Seite 22

WARNINGFOR YOUR SAFETYIf you smell gas:1. Open windows.2. DO NOT try to light any appliance.3. DO NOT use electrical switches.4. DO NOT use any teleph

Seite 23

© 2007 Roberts-Gordon, LLCAll rights reserved. No part of this work covered by the copyrights herein may be reproducedor copied in any form or by any

Seite 24

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL24 SECTION 12: SERVICING12.1 Servicing InstructionsAfter start-up, the heater will re

Seite 25 - Cut Hazard

SECTION 12: SERVICING2512.8 Maintenance ChecklistWARNINGExplosion HazardService and annual inspection must be done by acontractor qualified in the ins

Seite 26 - End View

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL26 Burner Observation WindowMake sure it is clean and free of cracks or holes.Clean a

Seite 27 - PERATION AND MAINTENANCE

SECTION 13: TROUBLESHOOTING27SECTION 13: TROUBLESHOOTING13.1 GeneralEnsure proper air flowclearance for axial fan.Open louvers slightly.Replace axial

Seite 28 - Electrical Shock Hazard

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL28 13.2 Troubleshooting For Automatic Ignition Burner SystemsIf problems persist, con

Seite 29 - SECTION 11: USER INSTRUCTIONS

SECTION 13: TROUBLESHOOTING2913.3 Troubleshooting for Flame Supervision SystemNOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3

Seite 30

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL30 13.4 Troubleshooting for Gas ValvesValve faulty.Replace with one ofcorrect type.Fa

Seite 31 - SECTION 12: SERVICING

SECTION 14: REPLACEMENT PARTS31SECTION 14: REPLACEMENT PARTSSee warnings and notes on Page 24, Section 12 before removing or replacing parts.Burner Co

Seite 32

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL32 14.2 Burner CompartmentRemove flexibleair duct from spigotRemoveaccess plateRemove

Seite 33 - 13.1 General

SECTION 14: REPLACEMENT PARTS3314.3 Ignition Electrode and Flame ProbeFlameProbeIgnitionElectrodeRemoveScrewIgnitionElectrodeBurnersFlameProbeBurnersB

Seite 35

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL34 14.4 Combustion Fan Vertical InstallationVent BoxOutletGasketFlue FanVent BoxScrew

Seite 36

SECTION 14: REPLACEMENT PARTS3514.5 Pressure SwitchPull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type o

Seite 37 - SECTION 14: REPLACEMENT PARTS

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL36 14.6 Ignition ControlThe control mounts to the electrical plate. Pull out ignition

Seite 38

SECTION 15: SPECIFICATIONS37SECTION 15: SPECIFICATIONS15.1 Standard (Models 150 - 400) UHA(S) Series Dimension DataABRear ViewEnd ViewZ25 1/2" (6

Seite 39

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL38 15.2 General Technical Data Table (All Models)ModelUHA[S]150UHA[S]175UHA[S]200UHA[

Seite 40

SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SE-39SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SERIES WARRANTYROBERTS-GORDON WILL PAY FOR:Within 24 mont

Seite 43 - SECTION 15: SPECIFICATIONS

10'(3 m)WARNING© 2007 Roberts-Gordon, LLC www.rg-inc.com

Seite 44

TABLE OF FIGURESFigure 1: Installation Clearances and Clearances to Combustibles...4Figure

Seite 46

SECTION 1: HEATER SAFETY1SECTION 1: HEATER SAFETYYour Safety is Important to Us! This symbol is used throughout the manual to notify you of possible

Seite 47

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL2 SECTION 2: INSTALLER RESPONSIBILITYThe installer is responsible for the following:•

Seite 48 - Max. Mounting Height*

SECTION 3: CRITICAL CONSIDERATIONS3SECTION 3: CRITICAL CONSIDERATIONS3.1 Basic InformationUHA(S) heaters have automatic ignition burners for ON/OFF op